Chiller plant fundamentals

HVAC concepts & terminology

A plain-language reference for the core ideas behind a chilled-water plant: what the numbers mean, what you can control, and where the energy goes.

1 Cooling capacity — TR and kW

How much heat a chiller can move — not how much electricity it uses.

Cooling capacity is measured in tons of refrigeration (TR). One ton is a fixed amount of heat-removal rate:

1 TR = 3.517 kW (thermal) = 3.517 kJ per second 100 TR = 351.7 kW = 351.7 kJ of heat removed every second

So a 100 TR chiller can pull 351.7 kW of heat out of the building every second.

Common misconception: a 100 TR chiller does not consume 351.7 kW of electricity. That number is its cooling capacity (heat moved). The electricity it actually draws is much smaller — often 60–80 kW — depending on how efficient it is.
Cooling capacity
351.7 kW
heat removed (thermal)
Electricity drawn
60–80 kW
depends on efficiency
The ratio of these two
efficiency
see section 2 →

2 Efficiency — kW/TR and COP

Two ways of expressing the same idea: heat moved per unit of electricity.

kW/TR lower is better

Electricity consumed per ton of cooling produced.

kW/TR = electricity consumed ÷ cooling produced = 70 kW ÷ 100 TR = 0.70

Meaning: it takes 0.70 kW of electricity to make 1 TR of cooling.

COP — coefficient of performance higher is better

Cooling output divided by electrical input (both in kW), so it's a pure ratio with no units.

COP = cooling output ÷ electrical input = 351.7 kW ÷ 70 kW = 5.02

Meaning: every 1 kW of electricity produces about 5 kW of cooling.

The two are just flip sides of each other: COP = 3.517 ÷ (kW/TR). Drag the slider to feel the relationship.
kW/TR 0.70 → COP 5.02

3 Plant dashboard & key terms

A typical at-a-glance view, and the vocabulary behind it.

Plant capacity
500 TR
Current load
420 TR
Power consumption
280 kW
Plant efficiency
0.67 kW/TR
280 ÷ 420
COP
5.25
3.517 ÷ 0.67

The vocabulary

TermUnitWhat it means
Plant cooling capacityTRMaximum heat the plant can remove
Plant power consumptionkWElectricity the plant draws right now
Plant efficiencykW/TRElectricity per ton of cooling (lower = better)
kW (thermal)kWHeat — 1 TR = 3.517 kW
kW (electrical)kWThe electricity the chiller draws to move that heat
Cooling loadTR / kWThe heat the building currently needs removed
ΔT (delta-T)°CDifference between return and supply chilled water
Flow rateL/sHow much water is being circulated
CHWR°CChilled-water return — warm water coming back from the building
Pump powerkWElectricity used by the circulating pumps
Two meanings of "kW": thermal kW is heat; electrical kW is power drawn. kW/TR is the ratio between them — keep the two clearly separated.

4 What you control vs. what you don't

Control levers can be set manually or by an AI optimizer; environment and demand are given.

you control

Control levers

Pump speed

CHWS setpoint (chilled-water supply temperature)

Cooling-tower fan speed

given to you

Environment & demand

Cooling load (building heat)

Outdoor wet-bulb temperature

Heat balance — why the condenser is bigger than the load

The chiller absorbs the building's heat and its own compressor's electrical work, then rejects the sum. For a 100 TR chiller drawing 70 kW:

Chiller 100 TR heat from building 351.7 kW electricity in 70 kW rejected at condenser/tower 421.7 kW
351.7 kW + 70 kW = 421.7 kW. The condenser must reject the cooling load plus the compressor's electrical work.

5 What determines plant efficiency

Where the electricity goes, and the knobs that move the numbers.

Where the power is consumed

Compressor 70–85%
Pumps 10–20%
Towers 5–15%
Compressor — largest consumer CHW + CW pumps — medium Cooling-tower fans — medium

The chiller itself contains the evaporator, compressor and condenser. Of the whole plant, the compressor dominates the electricity bill, which is why anything that eases the compressor's job (lower lift, better staging) saves the most.

Two water loops

(1) the chilled-water loop from the AHU, and (2) the condenser-water loop in and out of the cooling tower.

Levers that set condenser-water temperature

Colder condenser water lowers the compressor's lift and its power. These factors control it:

Cooling-tower fan speed
higher RPM → more heat rejection → colder water
Number of towers running
more surface area available for rejection
Condenser-water pump speed
flow from condenser to tower
Fouling (clean vs. dirty)
scale/dirt reduces heat transfer
Chiller staging
sharing load across machines for best efficiency

6 Where the biggest savings come from

In rough order of impact for most plants.

  1. Raise CHWS slightly when comfort allows — less lift, lower compressor power.
  2. Optimize cooling-tower fan speed — balance fan energy against colder, cheaper condenser water.
  3. Optimize chiller staging — run the right number of machines at their efficient load.
  4. Optimize pump speeds — circulate only as much water as the load needs.
  5. Maintain a proper ΔT — avoid the low-ΔT, over-pumping trap.

7 Overall components & flow

How heat travels from the rooms all the way out to the sky.

Chiller
evaporator · compressor · condenser
Pumps
CHW (chilled) · CW (condenser)
Fans
AHU fan · cooling-tower fan
Cooling tower rejects heat to air Chiller condenser compressor evaporator AHU coil + fan Bldg condenser loop chilled loop

The building generates heat (people, machines, sunlight). The AHU fan pulls that warm air across a cooling coil; cold water inside the coil absorbs the heat, so cool air returns to the rooms and the water leaves warm. The CHW pump sends that warm water to the chiller's evaporator, which chills it again — the difference between leaving and returning water is ΔT.

Inside the chiller, the compressor moves the absorbed heat from the evaporator to the condenser. Condenser water flowing through (driven by the CW pump) absorbs that heat and carries it to the cooling tower, which releases it to the atmosphere. Then the cycle repeats.